What this unit covers

MWA C, Installs, services and maintains wiring systems, is about 30 of the 100 exam questions: Task C-16 raceways, conductors, cables and enclosures (9), C-17 branch circuitry and devices (9), C-18 HVAC systems (4), C-19 electric heating (4), C-20 exit and emergency lighting (3) and C-21 cathodic protection (1). These are original, independent practice notes; they are not documents of the Red Seal Program, the CCDA or any provincial authority. Code questions are answered with your own copy of the Canadian Electrical Code 2024, supplied in the exam room; these notes do not reproduce its tables or values.

Conductors, cables and raceways

Branch circuits and devices

HVAC power and controls

Electric heating

Emergency lighting and cathodic protection

Take the free test · full question bank and mock exams with a subscription

Sample questions (5)

1. An apprentice is identifying the conductors of a new 120/240 V branch circuit. Which insulation colour normally identifies the grounded (neutral) conductor?

  1. Black or red insulation
  2. Orange or blue insulation
  3. White or grey insulation
  4. Green or bare copper

Conductors are identified and colour-coded according to the CEC requirements (RSOS sub-task C-16.01), and the grounded conductor is white or grey. Black and red identify ungrounded phase conductors, orange and blue do not identify the neutral, and green or bare copper identifies the bonding conductor.

2. An apprentice asks what a raceway does in a wiring system. What is its main function?

  1. Give access for splicing and terminating the conductors
  2. Support the conductors and protect them from damage
  3. Protect the conductors from overload and short circuit
  4. Raise the current rating of the conductors it holds

The RSOS states that “Raceways support and protect conductors” (RSOS task C-16): the raceway holds the conductors in place and shields them from physical damage. Access for splicing and terminating is given by the boxes and enclosures used with the raceway, protection from overload and short circuit comes from the overcurrent protection device, and a raceway does not raise the current rating of the conductors it holds.

3. A food plant washdown area is sprayed daily with hoses and corrosive sanitizing chemicals. Which enclosure type suits a control box installed there?

  1. NEMA Type 1
  2. NEMA Type 3R
  3. NEMA Type 4X
  4. NEMA Type 12

A Type 4X enclosure is watertight against hose-directed water and resists corrosion, so it suits a washdown area (RSOS sub-task C-16.04, CSA/NEMA classification). Type 1 is for indoor general use with no water protection, Type 3R protects against falling rain and ice outdoors but not hose spray, and Type 12 protects against dust and dripping non-corrosive liquids indoors.

4. An electrician is pulling conductors through a long conduit run with three bends and the pulling tension is getting high. Which action correctly reduces the tension?

  1. Coat the insulation with thread-cutting oil
  2. Use a lubricant made for the insulation type
  3. Spread anti-oxidant compound along the conductors
  4. Pull the conductors faster with a power winch

A pulling lubricant compatible with the insulation lowers the friction in the conduit and so the pulling tension (RSOS sub-task C-16.01). Thread-cutting oil is not made for pulling and can damage the insulation, anti-oxidant compound is meant for aluminum terminations and does not lubricate the pull, and pulling faster does not reduce the friction and risks exceeding the manufacturer’s maximum pulling tension.

5. An electrician prepares a large aluminum conductor for a mechanical lug. Which step is specific to aluminum conductors?

  1. Tin the strands with solder before inserting them
  2. Coat the strands with a thin film of lubricating oil
  3. Leave the oxide film on to protect the strands
  4. Brush the strands, then apply anti-oxidant compound

Aluminum forms an oxide film that resists current flow, so the strands are brushed clean and treated with anti-oxidant compound before termination (RSOS sub-task C-16.01, preparation of aluminum conductors). Soldering aluminum strands is not a valid termination method, oil does not remove the oxide, and leaving the film on causes a high-resistance, overheating joint.

Start free