What this unit covers
Major Work Activity D of the 2025 RSOS: installing, servicing and maintaining motors and control systems. Its tasks carry 21 of the 100 exam questions: motor starters and controls (D-22, 8), drives (D-23, 4), motors (D-24, 6) and automated control systems (D-25, 3). These are original, independent practice notes; they are not documents of the Red Seal Program, the CCDA or any provincial authority. Code questions are answered with your own copy of the Canadian Electrical Code 2024, provided in the exam room; these notes reproduce none of its tables or values.
Starters
- Forward/reverse starter: reversing swaps two line conductors, so a mechanical interlock stops both contactors closing together and shorting the supply (RSOS sub-task D-22.01).
- Wye-delta starting: both ends of each winding must reach the terminal box; in wye, starting line current and starting torque fall to about one third of across-the-line values (RSOS sub-task D-22.01).
- Overload relay: responds to current that stays above the motor full load rating long enough to heat the windings; short-circuit protection is a separate overcurrent device (RSOS sub-task D-22.02).
Control circuits and troubleshooting
- Three-wire control: the holding contact drops out on power failure, so the motor needs a new start command (low-voltage protection); two-wire control restarts automatically (RSOS sub-task D-22.03).
- Multiple stations: start buttons and the holding contact in parallel, stop buttons in series (RSOS sub-task D-22.03).
- Emergency stop: a normally closed contact in series is fail-safe (RSOS sub-task D-22.03).
- Timers: an on-delay (TON) contact changes state after the set time from energization; an off-delay (TOF) contact changes immediately and times after de-energization (RSOS sub-task D-22.03).
- Voltmeter test: in a series circuit, full control voltage across a contact means that contact is open (RSOS sub-task D-22.04).
- Isolation: a selector switch only opens the control circuit; lock out the bucket isolating switch and verify absence of voltage with a tester (RSOS sub-task D-22.02).
Drives
- AC drive: the rectifier converts AC to DC for the DC bus; the inverter feeds the motor (RSOS sub-task D-23.01).
- Bus capacitors: wait the discharge time marked on the drive, then measure the DC bus (RSOS sub-task D-23.02).
- Short deceleration: the motor regenerates onto the DC bus; lengthen the time or add a dynamic braking resistor (RSOS sub-task D-23.02).
- Speed: induction motor speed follows frequency, not voltage; below base speed a DC drive lowers armature voltage, and field weakening raises speed (RSOS sub-tasks D-23.02 and D-23.03).
Motors
- Synchronous speed: 120 × frequency / number of poles; a synchronous motor has zero slip (RSOS sub-task D-24.03).
- Reversing: single-phase, reverse one winding only; DC, reverse the armature or the field, not both (RSOS sub-tasks D-24.01 and D-24.05).
- Single phasing: the motor keeps turning but current rises and windings overheat (RSOS sub-task D-24.04).
- Nameplate: service factor = continuous multiplier of rated power; code letter = locked-rotor kVA per horsepower; insulation class = winding temperature rating (RSOS sub-task D-24.04).
- Series DC motor: never run unloaded; speed rises to a dangerous level (RSOS sub-task D-24.05).
- Power: watts = horsepower × 746; efficiency = output / input × 100.
PLCs
- Scan: read inputs to memory, solve the logic, write the outputs (RSOS sub-task D-25.01).
- XIC and XIO: XIC is true while the bit is ON, XIO while it is OFF (RSOS sub-tasks D-25.01 and D-25.03).
- 4-20 mA: signal = 4 + 16 × (measured value / range); 4 mA is the live zero (RSOS sub-task D-25.01).
- Forcing: a forced output ignores interlocks and logic (RSOS sub-task D-25.02).
Sample questions (5)
1. What is the purpose of the mechanical interlock fitted between the forward and reverse contactors of a reversing motor starter?
- To delay the reverse contactor until the motor has stopped turning
- To hold the forward contactor closed after the start button is released
- To physically prevent both contactors from closing at the same time
- To trip the starter when the motor draws more than its rated current
Reversing swaps two line conductors, so two contactors closed together would short-circuit the supply; the mechanical interlock blocks this physically (RSOS sub-task D-22.01, forward/reverse starter). A delay before reversing is a timer function, the holding contact keeps the coil energized, and tripping on excess current is the job of the overload relay.
2. In a three-wire motor control circuit, what is the function of the holding (seal-in) contact connected across the start pushbutton?
- To keep the starter coil energized after the start button is released
- To open the coil circuit when the overload relay detects excess current
- To reduce the voltage applied to the coil once the starter has closed
- To let the motor restart by itself as soon as power is restored
The normally open holding contact closes when the starter picks up and bypasses the start button, so the coil stays energized (RSOS sub-task D-22.03, low-voltage protection). Opening the circuit on excess current is the overload contact, a coil economizer is a different device, and automatic restart is a feature of two-wire control, not of three-wire control.
3. Against which condition does the overload relay of a motor starter protect the motor?
- A bolted short circuit at the load terminals of the starter
- A loss of control voltage at the starter coil terminals
- A brief current surge each time the motor is started
- A sustained current above the full load rating of the motor
An overload relay responds to current that stays above the motor full load rating long enough to heat the windings (RSOS sub-task D-22.02, overload settings). Short-circuit protection is provided by a separate overcurrent device, a loss of coil voltage simply drops the contactor out, and the relay is designed to ride through the normal starting surge.
4. A conveyor motor must be started from two separate operator stations using three-wire control. How are the two start pushbuttons connected?
- In parallel with each other and with the holding contact
- In parallel with each other but in series with the holding contact
- In series with each other and in series with the holding contact
- In series with each other and in parallel with the holding contact
Run (start) devices are connected in parallel so that any one of them can energize the coil, and the holding contact is in parallel with them (RSOS sub-task D-22.03, multiple location control). Start buttons in series would require both to be pressed, and a holding contact in series with them would prevent the coil from ever being energized. Stop buttons from each station go in series.
5. An electrician sets the adjustable overload relay of a new motor starter. Which information is used as the basis for the setting?
- The full load current shown on the motor nameplate
- The current rating of the contactor shown on the starter
- The locked rotor current worked out from the motor code letter
- The rating of the overcurrent device ahead of the starter
The overload relay is set from the full load current on the motor nameplate, with any adjustment made according to the CEC requirements (RSOS sub-task D-22.01, set up and adjust motor overloads, nameplate data). The contactor rating, the locked rotor current and the branch circuit overcurrent rating all describe other limits and would leave the motor unprotected against a sustained overload.