Practice questions written by us, with the correct answer and the rule cited. They are not official questions.

1. During a pre-use inspection, an electrician finds frayed stitching on the shoulder strap of a full body harness. What must be done with the harness?

  1. Use it for restraint work close to the ground
  2. Tag it as defective and take it out of service
  3. Repair the stitching on site with strong thread
  4. Use it with a second lanyard added as a backup

RSOS sub-task A-1.01 requires faulty PPE to be replaced or tagged and removed from service, and section 26.6 of O. Reg. 213/91 requires a defective fall arrest component to be taken out of service immediately. Section 26.4 of O. Reg. 213/91 applies the same rule to a travel restraint system, a field repair with thread is not a manufacturer repair, and a second lanyard does not make a damaged harness safe.

2. The current leads of a meter on a CT-metered 347/600 V service must be disconnected for repair while the service stays energized and loaded. What is done first?

  1. Open the CT secondary leads so that the CT is isolated
  2. Install a shorting link across the CT secondary terminals
  3. Fit a fuse in the CT secondary to limit the current
  4. Connect a resistor across the meter voltage terminals

A CT secondary must stay closed while the primary carries load, so a shorting link is installed before the leads come off (RSOS sub-task B-7.04 covers servicing metering equipment). An open secondary develops a dangerous high voltage, a fuse can open the circuit and cause the same hazard, and a resistor across the voltage terminals does nothing for the current circuit.

3. An apprentice is identifying the conductors of a new 120/240 V branch circuit. Which insulation colour normally identifies the grounded (neutral) conductor?

  1. Black or red insulation
  2. Orange or blue insulation
  3. White or grey insulation
  4. Green or bare copper

Conductors are identified and colour-coded according to the CEC requirements (RSOS sub-task C-16.01), and the grounded conductor is white or grey. Black and red identify ungrounded phase conductors, orange and blue do not identify the neutral, and green or bare copper identifies the bonding conductor.

4. A sump pump is controlled by a float switch through a two-wire control circuit. What happens when power returns after an outage while the water level is high?

  1. The pump stays off until an operator presses the start pushbutton
  2. The pump restarts automatically since the float switch is closed
  3. The pump restarts once the overload relay has been manually reset
  4. The pump stays off because the holding contact has opened

In two-wire control (low-voltage release) the maintained float contact alone holds the coil energized, so the starter closes again as soon as voltage returns (RSOS sub-task D-22.03). There is no start button or holding contact in this circuit, and the overload relay has not tripped because of an outage.

5. After a ground fault relay and sensor are installed on a main breaker, the electrician must prove that the system works. What must be verified?

  1. The breaker trips at its rated load current with no fault present
  2. The neutral and bonding conductors are tied together at the sensor
  3. The relay resets itself when the simulated fault is removed
  4. The system trips or alarms when a test fault is simulated

The ground fault system is tested to confirm that it trips or alarms as set when a fault is simulated (RSOS sub-task B-11.02). A breaker that trips at rated current with no fault is a nuisance trip, tying the neutral to the bonding conductor at the sensor defeats the sensing, and automatic reset is not what the test is meant to prove.

6. A dimmed LED luminaire flickers and buzzes when it is controlled by an old incandescent-type dimmer. What should the electrician do?

  1. Fit a dimmer rated for LED loads and compatible with the driver
  2. Connect the dimmer in the neutral conductor to reduce the flicker
  3. Add a higher-wattage lamp on the circuit to stabilize the load
  4. Replace the driver with a magnetic ballast of the same wattage

An LED driver must be paired with a dimmer rated for LED loads and compatible with that driver, as required when lighting control components are selected in RSOS sub-task C-17.03. Dimming the neutral is unsafe, adding a higher-wattage lamp wastes energy and does not cure the incompatibility, and a ballast cannot power an LED array.

7. A camera on an exterior wall is powered through Power over Ethernet. The camera shows no video and no power, and a cable analyzer shows the cable is good. What should be checked next?

  1. That the camera has its own 120 V supply wired from the nearest panel
  2. That the cable is terminated with coaxial connectors at both ends
  3. That the recorder has free analog input channels available for the camera
  4. That the network switch port or injector supplies PoE to the camera

With PoE, one network cable carries both data and power, so after the cable is proven good the next check is that the switch port or injector actually supplies power (RSOS sub-task E-26.03). A separate 120 V supply is not needed, an IP camera uses twisted-pair cabling with modular plugs rather than coaxial connectors, and analog recorder inputs are not used by an IP camera.

8. Given the following information: - Pressure transmitter range: 0 to 250 kPa - Output signal: 4-20 mA, linear - Measured pressure: 100 kPa What is the loop current, in milliamperes, rounded to one decimal place?

  1. 6.4 mA
  2. 8.0 mA
  3. 10.4 mA
  4. 13.6 mA

The signal is 4 + 16 × (100 / 250) = 4 + 6.4 = 10.4 mA (RSOS sub-task D-25.01). Omitting the 4 mA live zero gives 6.4 mA, multiplying the fraction by 20 mA instead of the 16 mA span gives 8.0 mA, and using the 150 kPa remaining below full scale instead of the measured 100 kPa gives 4 + 16 × (150 / 250) = 13.6 mA.

9. A customer wants added protection from shock where a leaking appliance could energize a wet kitchen counter. Which device protects people against this hazard?

  1. A GFCI receptacle on the counter circuit
  2. An AFCI breaker in the main panel
  3. A surge protective device at the service
  4. A time-delay fuse at the branch circuit

RSOS sub-task B-8.02 covers ground fault protection devices, and a GFCI opens quickly when current leaks to ground, for example through a person. An AFCI detects arcing in wiring, an SPD diverts voltage surges, and a time-delay fuse protects conductors against overload without sensing leakage.

10. During a maintenance visit, the lamp heads of an emergency lighting unit do not light on test and its charging indicator is off. Which action should the electrician take first?

  1. Check with a multimeter for supply voltage at the unit input terminals
  2. Replace the lamp heads with new ones taken from the maintenance stock
  3. Replace the battery with a new one before taking any measurement
  4. Connect the battery directly to the lamp heads and bypass the charger

The source of a malfunction is determined from field assessments and diagnostic equipment results, such as multimeter readings (RSOS sub-task C-20.02). With the charging indicator off, the first check is whether the unit is actually supplied. Replacing lamp heads or the battery without a measurement is guessing, and bypassing the charger removes a component without finding the cause.

11. An electrician will measure voltage at a 600 V service panel with a multimeter. What must be checked on the meter before it is used there?

  1. Its display resolution and number of digits
  2. Its auto-ranging and data-logging functions
  3. Its battery type and its expected battery life
  4. Its category (CAT) rating and voltage rating

Correct answer: “Its category (CAT) rating and voltage rating”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

12. Given the following information about a single-phase transformer: - primary voltage: 600 V - secondary voltage: 240 V - primary current: 20 A What is the secondary current?

  1. 8.0 A
  2. 20.0 A
  3. 50.0 A
  4. 125.0 A

Correct answer: “50.0 A”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

13. An electric furnace has three heating elements controlled by a sequencer. What is the purpose of the sequencer on a call for heat?

  1. It energizes every element together so full capacity is reached immediately
  2. It lowers the voltage applied to each element in three equal steps
  3. It opens the elements in turn so that one stays energized at a time
  4. It energizes the elements one after another so the load comes on in stages

Correct answer: “It energizes the elements one after another so the load comes on in stages”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

14. The field circuit of a DC shunt motor that is run by a DC drive opens because of a broken field lead while the motor is running. What is the main hazard?

  1. The motor reverses because the field polarity is lost
  2. The motor stops because the armature current falls to zero
  3. The motor overspeeds because the field flux collapses
  4. The motor slows sharply because the back EMF disappears

Correct answer: “The motor overspeeds because the field flux collapses”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

15. An aluminum feeder conductor is to be landed on a switchboard lug rated for aluminum. What must be done after the insulation is removed?

  1. Solder the bare strands so they keep their shape
  2. Leave the strands bare so the lug can bite in
  3. Apply antioxidant compound to the bare strands
  4. Coat the strands in general-purpose grease

Correct answer: “Apply antioxidant compound to the bare strands”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

16. During an office upgrade, an electrician finds a junction box above a finished ceiling with no access panel. What must be done?

  1. Cover the box and mark it on the drawings
  2. Plaster over the box and seal the cover
  3. Leave the box and note it in the maintenance log
  4. Relocate the box or add an access panel

Correct answer: “Relocate the box or add an access panel”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

17. An electrician terminates one end of a Category 6 patch cord with the T568B pin assignment. How must the other end be terminated for a straight-through cord?

  1. With the T568A assignment, which reverses the pairs end to end
  2. With the pairs in whatever order is convenient on site
  3. With the T568B assignment, matching the first end exactly
  4. With a rolled assignment that reverses the eight positions

Correct answer: “With the T568B assignment, matching the first end exactly”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

18. Two identical photovoltaic modules are connected in series to form a string. How does the string compare with a single module?

  1. The voltages add and the current stays the same
  2. The currents add and the voltage stays the same
  3. Both the voltage and the current add together
  4. The voltage stays the same and the current is halved

Correct answer: “The voltages add and the current stays the same”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

19. To test a conveyor motor starter, an electrician forces a PLC output ON from the programming terminal. What is the main hazard of this forcing?

  1. The stored program is replaced by the state that was forced
  2. The CPU stops scanning until the force has been removed
  3. The output ignores the logic, so equipment may start unexpectedly
  4. The output module is permanently damaged by the state that was forced

Correct answer: “The output ignores the logic, so equipment may start unexpectedly”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

20. A duct heater's manual-reset high-limit switch keeps tripping. What should the electrician do before resetting it again?

  1. Install a jumper across the limit so the heater can run under test load
  2. Find and correct the cause, such as restricted airflow, before it is reset
  3. Replace the limit with a unit that has a higher temperature setting
  4. Reset it again and record the element current during the next cycle

Correct answer: “Find and correct the cause, such as restricted airflow, before it is reset”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

21. An electrician is about to energize a new switchgear lineup when a labourer is still working inside the equipment room. What must be done?

  1. Energize it and warn the labourer to stay clear of live parts
  2. Ask the labourer to stand near the exit while the feeder is closed
  3. Energize it from a remote station if the labourer wears insulated gloves
  4. Stop and confirm that all personnel are notified and clear of the area

Correct answer: “Stop and confirm that all personnel are notified and clear of the area”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

22. A UPS battery room holds vented lead-acid cells that release hydrogen while charging. What must the installation provide?

  1. Ventilation that prevents hydrogen build-up
  2. A sealed room that keeps the gas held inside
  3. Luminaires with lamps open to the room air
  4. A humidifier that keeps the cell tops damp

Correct answer: “Ventilation that prevents hydrogen build-up”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

23. What does an inductive loop vehicle detector at a signalized intersection sense?

  1. A change in loop resistance caused by the weight of a vehicle
  2. A change in light level at the sensor caused by headlights
  3. A change in loop voltage caused by tire vibration
  4. A change in loop inductance caused by the metal of a vehicle

Correct answer: “A change in loop inductance caused by the metal of a vehicle”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

24. An electrician wires a start/stop station for a three-wire control circuit. Which contact type is used for the stop pushbutton, and how is it connected?

  1. Normally open, in parallel with the starter coil
  2. Normally closed, in series with the starter coil
  3. Normally closed, in parallel with the start pushbutton
  4. Normally open, in series with the holding contact

Correct answer: “Normally closed, in series with the starter coil”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

25. After a generator replaces the utility feed, three-phase motors rotate backwards although they turned correctly on utility power. What is the likely cause?

  1. The phase sequence of the generator is reversed
  2. The generator frequency is set a little too high
  3. The voltage regulator is holding the voltage low
  4. The generator neutral is not bonded to ground

Correct answer: “The phase sequence of the generator is reversed”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

26. An electrician calculates the distance between the two bends of an offset from the offset height and the bend angle. Which function of the bend angle is the multiplier?

  1. Cosecant of the offset bend angle
  2. Sine of the offset bend angle
  3. Cosine of the offset bend angle
  4. Tangent of half the bend angle

Correct answer: “Cosecant of the offset bend angle”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

27. An electrician must trigger the fire alarm interface of an integrated control system for a test. What prevents an unintended discharge of the fire suppression system?

  1. Testing late at night, when fewer people are in the building
  2. Disabling the release circuit first and restoring it after the test
  3. Asking the operator to watch the suppression panel during the test
  4. Using test signals that are smaller than the real alarm signals

Correct answer: “Disabling the release circuit first and restoring it after the test”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

28. An electrician is about to attach a safety ground to a high-voltage disconnect that was just opened. What must be done before the safety ground is attached?

  1. Test the equipment and establish that it is isolated from its source
  2. Confirm visually that the switch handle is in the open position
  3. Place a second safety ground on the load side of the disconnect
  4. Inform the control room that the disconnect is open, then attach it

Correct answer: “Test the equipment and establish that it is isolated from its source”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

29. A belt-driven series DC motor loses its belt and runs with no load. What is the main hazard?

  1. The motor stops because the field current falls to zero
  2. The speed rises dangerously and can destroy the armature
  3. The speed stays near rated value since the field is constant
  4. The motor reverses because the load torque is removed

Correct answer: “The speed rises dangerously and can destroy the armature”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.

30. A hallway luminaire must be controlled from three locations. Which switch arrangement is used?

  1. A four-way switch at each end and a three-way in the centre
  2. A three-way switch at each end and a four-way switch between them
  3. Three single-pole switches wired in series with the luminaire
  4. Three three-way switches sharing the same pair of travellers

Correct answer: “A three-way switch at each end and a four-way switch between them”. In this free mini exam, full explanations are shown on the first 10 questions only; the complete reasoning and the RSOS reference for this question come with Premium access.